DCW 150-12FT-P6611

DCW 150-12FT-P6611. This rugged, industrial quality DC/DC converter uses field proven topology to generate 150W output power.

Refurbished and tested. Ask for price and availability on WhatsApp: +1 (469) 684-5039.

This rugged, industrial quality DC/DC converter uses field proven topology to generate 150W output power. It is a mature design with a track record in hundreds of applications. This chassis-mount design is also optimized for cost efficiency. Cooling is via baseplate to a heat-sinking surface and by natural convection. Additional ruggedizing and conformal coating are available for applications that require higher immunity to shock, vibration and humidity. Low component count, large design headrooms, and the use of components with established reliability result in a high MTBF. The DCW 150 is manufactured at our plant under strict quality control.

SPECIFICATIONS

Input Voltage Two standard input ranges are available: 20 - 60Vdc or 65 - 160Vdc Consult factory for other input voltages and ranges

Input Protection Inrush current limiting Varistor Reverse polarity protection Internal safety fuse Lower voltage than the specified minimum input will not damage the unit.

Isolation 1500VDC input to chassis, 1500VDC input to output, 500VDC output to chassis

Standards Designed to meet EN 60950 and related standards

EMI EN55022 Class A with margins

Switching Frequency 55kHz +/- 3kHz

Output Voltage 12V, 24V, 48V or 125Vdc Consult factory for other voltages

Redundancy diode Not installed Available as option

Line/Load Regulation +/-1% combined

Dynamic Response Max 5% voltage deviation for 10% to 50% load step, with better than 1msec recovery time

Output Ripple/Noise Better than 1% of output voltage peak to peak or 0.2% RMS of the output voltage (20MHz BW)

Overload Protection Current limiting with short circuit protection (hiccup type) Thermal shut-down with automatic recovery in case of insufficient cooling.

Output Overvoltage Protection Double regulator loop

Efficiency Output voltage dependent Typically 80% at full load

Operating Temperature 0°C to 50°C for full specification Wider temperature ranges available

Temperature Drift 0.03% per oC over operating temperature range

Cooling Conduction to customer heatsink or chassis and natural convection

Environmental Protection Basic ruggedizing Optional heavy ruggedizing and conformal coating is available

Shock/Vibration IEC 61373 Cat 1 A&B

Humidity 5 – 95% non-condensing

MTBF 140,000 hours @ 45oC Demonstrated MTBF is significantly higher

Indicators Green “Power ON” LED, visible through the cooling slots.